Rated Control Power Supply Voltage
Rated Control Power Supply Voltage Us(V) AC 220/230/240
AC 380/400/415
DC220, DC110
AC110 (not available for NXA16)
1600A frame CC&ST
Operation Voltage(V) Close time (ms)
(0.85-1.1) Us <50 NXA16
Power consumption (VA/W) NXA20~63
Rated control power supply voltage Us(V) AC 220/230/240
AC 380/400/415
DC220
DC110
AC110 (not available for NXA16)
1600A frame CC&ST
Operation Voltage(V) Close time (ms)
(0.85-1.1) Us
<50
NXA16
Power consumption
(VA/W) NXA20~63
Notes:
2000A-6300A frame CC&ST
- It must select pulse type in the automatic control system.
- power-on time of the intermittent type cannot be greater than 2 s, pulse frequency of the pulse type cannot be more than 5 times/min, or the components are easily burnt.
- Ensure that the product is in the energy storage state so that the closed electromagnet may be energized;
- If the product is not closed after a single power-on for 15s, must disconnect the power on the closed electromagnet immediately.
- Shunt release (ST)
The power-on time cannot be greater than 2 seconds/ time, and the power-on frequency cannot be greater than 5 times / minute.
a. The shunt release should be used except for special products where the circuit breaker must be directly disconnected manually;
b. The shunt release could operate within 10 meters to break the circuit breaker.
AC110
Rated control power supply voltage Us(V) AC 220/230/240
AC 380/400/415
DC220
DC110
(not available for NXA16)
Operation Voltage(V)
(0.7-1.1) Us
Break time (ms)
≤28
NXA16
Power consumption
(VA/W) NXA20-63
pulse intermittent pulse
Notes:
- It must select pulse type in the automatic control system.
- power-on time of the intermittent type cannot be greater than 2 s, pulse frequency of the pulse type cannot be more than 5 times/min, or the components are easily burnt;
- If the circuit breaker is not break by a single power-on of 15 s, must disconnect the power on the shunt release immediately.
Functions and features | Air Circuit Breaker
P-022
- Undervoltage release (UVT)
Under-voltage release (UVT) (Optional, the power must be turned on before the circuit breaker is closed)
The under-voltage release has instantaneous operation and delayed operation:
Operation types of each frame under-voltage release
Self-priming
Helped priming
Under-voltage instantaneous release
Inm=1600A, 6300A
Inm=2000A, 3200A, 4000A
Inm=1600A, 6300A
Inm=2000A, 3200A, 4000A
1600A frame UVT 2000-4000A frame UVT
Under-voltage delay release.
Notes:
- Inm=1600A under-voltage delay does not require an external delay controller. The power-off operation is an instantaneous operation. There is no zero-voltage delay function;
- Inm=6300A under-voltage delay does not require an external under-voltage delay controller. There is a delay function for low voltage and power off;
- Inm=2000A~4000A under-voltage delay requires an external delay controller. There is a delay operation when the power is off. There is a zero-voltage delay function.
Delay time of under-voltage release
Inm=1600A Inm=2000A~4000A
Delay time (optional)
1 s, 3 s, 5 s, 7 s (not adjustable)
1 s, 3 s, 5 s (not adjustable)
6300A frame ASUVT
Accuracy ±15%
0~1s
±15%
Inm=6300A
0.3 s~7.5 s (adjustable)
The under-voltage will not operate when the voltage returns to 85% Ue and higher, within 1/2 delay time.