Rated Control Power Supply Voltage

In stock

Rated Control Power Supply Voltage Us(V) AC 220/230/240
AC 380/400/415
DC220, DC110
AC110 (not available for NXA16)
1600A frame CC&ST
Operation Voltage(V) Close time (ms)
(0.85-1.1) Us <50 NXA16
Power consumption (VA/W) NXA20~63
 

SKU: Rated-Control-Power-Supply-Voltage Category:

Rated control power supply voltage Us(V) AC 220/230/240
AC 380/400/415
DC220
DC110
AC110 (not available for NXA16)
1600A frame CC&ST
Operation Voltage(V) Close time (ms)
(0.85-1.1) Us
<50
NXA16
Power consumption
 (VA/W) NXA20~63
Notes:
2000A-6300A frame CC&ST

  1. It must select pulse type in the automatic control system.
  2. power-on time of the intermittent type cannot be greater than 2 s, pulse frequency of the pulse type cannot be more than 5 times/min, or the components are easily burnt.
  3. Ensure that the product is in the energy storage state so that the closed electromagnet may be energized;
  4. If the product is not closed after a single power-on for 15s, must disconnect the power on the closed electromagnet immediately.
  • Shunt release (ST)
    The power-on time cannot be greater than 2 seconds/ time, and the power-on frequency cannot be greater than 5 times / minute.
    a. The shunt release should be used except for special products where the circuit breaker must be directly disconnected manually;
    b. The shunt release could operate within 10 meters to break the circuit breaker.
    AC110
    Rated control power supply voltage Us(V) AC 220/230/240
    AC 380/400/415
    DC220
    DC110
    (not available for NXA16)
    Operation Voltage(V)
    (0.7-1.1) Us
    Break time (ms)
    ≤28
    NXA16
    Power consumption
    (VA/W) NXA20-63
    pulse intermittent pulse
     
     
    Notes:
  1. It must select pulse type in the automatic control system.
  2. power-on time of the intermittent type cannot be greater than 2 s, pulse frequency of the pulse type cannot be more than 5 times/min, or the components are easily burnt;
  3. If the circuit breaker is not break by a single power-on of 15 s, must disconnect the power on the shunt release immediately.
    Functions and features | Air Circuit Breaker
    P-022
  • Undervoltage release (UVT)
    Under-voltage release (UVT) (Optional, the power must be turned on before the circuit breaker is closed)
    The under-voltage release has instantaneous operation and delayed operation:
    Operation types of each frame under-voltage release
    Self-priming
    Helped priming
    Under-voltage instantaneous release
    Inm=1600A, 6300A
    Inm=2000A, 3200A, 4000A
    Inm=1600A, 6300A
    Inm=2000A, 3200A, 4000A
    1600A frame UVT 2000-4000A frame UVT
    Under-voltage delay release.
     
    Notes:
  1. Inm=1600A under-voltage delay does not require an external delay controller. The power-off operation is an instantaneous operation. There is no zero-voltage delay function;
  2. Inm=6300A under-voltage delay does not require an external under-voltage delay controller. There is a delay function for low voltage and power off;
  3. Inm=2000A~4000A under-voltage delay requires an external delay controller. There is a delay operation when the power is off. There is a zero-voltage delay function.
    Delay time of under-voltage release
    Inm=1600A Inm=2000A~4000A
    Delay time (optional)
    1 s, 3 s, 5 s, 7 s (not adjustable)
    1 s, 3 s, 5 s (not adjustable)
    6300A frame ASUVT
    Accuracy ±15%
    0~1s
    ±15%
    Inm=6300A
    0.3 s~7.5 s (adjustable)
    The under-voltage will not operate when the voltage returns to 85% Ue and higher, within 1/2 delay time.